A sign outlet is assigned a minimum allowance of ____ volt-amperes for each branch circuit required.

You’re reading an outdated article. Please go to the recent issues to find up-to-date content.

Article 220 C Load Calculations  

220.14 Other Loads—All Occupancies

Knowing how to perform load calculations in accordance with the National Electrical Code (NEC) plays a significant role in an electrician’s professional career. Before installing branch circuits, feeders or services on a job, loads must be calculated. Branch-circuit load calculation requirements are in Part II of Article 220.

After calculating branch-circuit loads, conductor sizes and ratings for overcurrent protection must be determined. Results from calculations in Part II of Article 220 are used in conjunction with specifications from 210.19 to size branch-circuit conductors. Sizing of branch-circuit overcurrent protective devices must be done in accordance with 210.20 and Part II of Article 220.

To size feeder (and service) conductors and overcurrent protection, loads must first be calculated in accordance with Part III or Part IV of Article 220. Last month’s column concluded by covering fixed multioutlet assemblies in 220.14(H). This month, the discussion continues with more requirements for general-use receptacles and outlets not used for general illumination.

Load calculations for receptacle outlets are covered in 220.14(I), (J), and (K). A receptacle, as defined in Article 100, is a contact device installed at the outlet for the connection of an attachment plug. A single receptacle is a single contact device with no other contact device on the same yoke. A multiple receptacle is two or more contact devices on the same yoke (see Figure 1). Sometimes there is confusion pertaining to a single duplex receptacle on a branch circuit with no other devices.

Although a duplex receptacle is installed and mounted by one strap or yoke, it is considered two receptacles. A branch circuit supplying only a duplex receptacle and no other device is not an individual branch circuit. An individual branch circuit, as defined in Article 100, is a branch circuit that supplies only one utilization equipment.

Except for dwelling occupancies and, under certain conditions, banks and office buildings, the calculated load for receptacle outlets is 180 volt-amperes for each single or for each multiple receptacle on one yoke. The load calculation for a single receptacle is 180 volt-amperes. The load calculation for a duplex receptacle is 180 volt-amperes. The load for three receptacles on one yoke or strap is also calculated at 180 volt-amperes (see Figure 2).

To calculate receptacles in accordance with 220.14(I), multiply the number of receptacles by 180 volt-amperes. For example, what is the calculated load for 30 15-ampere duplex receptacles in a retail store? Multiply the number of receptacles by 180 (30 × 180 = 5,400). The minimum calculated load for 30 15-ampere duplex receptacles in a retail store is 5,400 volt-amperes. The calculated load for 20-ampere receptacle outlets is no different than the calculated load for 15-ampere receptacle outlets. For example, what is the calculated load for 30 20-ampere duplex receptacles in a retail store? Although 20-ampere receptacles have a higher rating than 15-ampere receptacles, the calculated load is exactly the same. The minimum calculated load for 30 20-ampere duplex receptacles in a retail store is 5,400 volt-amperes (30 × 180 = 5,400) (see Figure 3).

The calculated load is used to determine the maximum number of receptacles permitted on a branch circuit in all but dwelling occupancies. The ampere rating of the overcurrent protective device is what determines the maximum number of receptacles on a branch circuit. For example, the maximum number of receptacles on a 15-ampere breaker (or fuse), supplied by a nominal source voltage of 120, is 10.

The calculation can be performed either by converting the ampacity rating to volt-amperes or by converting volt-amperes to amperes. Use Ohm’s Law to find amperes when volt-amperes and voltage are known (I = W ÷ E). Divide 180 by 120. The calculated load for one receptacle supplied by 120 volts is 1.5 amperes (180 ÷ 120 = 1.5).

To find the maximum number of receptacles permitted on a 15-ampere breaker, divide the rating of the breaker by 1.5 amperes (15 ÷ 1.5 = 10). The maximum number of receptacles permitted on a 15-ampere, 120-volt breaker is 10 (see Figure 4). Because of provisions in Table 210.21(B)(3) and Table 210.24, 20-ampere receptacles are not permitted on a branch circuit having a rating of 15-amperes.

Because of the higher rating on a 20-ampere breaker, more receptacles are permitted than on 15-ampere overcurrent devices. The calculated load per receptacle is the same, 1.5 amperes. To find the maximum number of receptacles permitted on a 20-ampere breaker, divide the rating of the breaker by 1.5 amperes (20 ÷ 1.5 = 13.3 = 13). The maximum number of receptacles permitted on a 20-ampere, 120-volt breaker is 13 (see Figure 5). In accordance with Tables 210.21(B)(3) and 210.24, these receptacles can be 15-ampere, 20-ampere or any combination thereof.

Although a single receptacle and duplex receptacle do not share the exact same definition, they are counted the same in a load calculation. Unless specifically stated in 220.14(J) and (K), receptacle outlets shall be calculated at not less than 180 volt-amperes for each single or for each multiple receptacle on one yoke [220.14(I)]. For example, what is the branch-circuit load calculation for 30 15-ampere single receptacles in a retail store? The calculated load for 30 15-ampere single receptacles is the same as it would be for 30 15-ampere duplex receptacles, 5,400 volt-amperes (30 × 180 = 5,400) (see Figure 6).

Some companies manufacture a single device containing four receptacles. Since there are four receptacles associated with this single piece of equipment, the load calculation is different. A single piece of equipment consisting of a multiple receptacle composed of four or more receptacles must be calculated at not less than 90 volt-amperes per receptacle [220.14(I)]. For example, what is the load calculation for a quad receptacle manufactured as a single device? Multiply the number of receptacles by 90 volt-amperes (4 × 90 = 360). Because there are four outlets in this single piece of equipment, the calculated load is 360 volt-amperes (see Figure 7).

Two duplex receptacles in the same box and under one double-duplex receptacle cover plate, also has a calculated load of 360 volt-amperes. Not because it is one piece of equipment, but because the receptacle outlets are on two different yokes (2 × 180 = 360). Likewise, two single receptacles in the same box and under one cover must be calculated at 360 volt-amperes.

The last sentence in 220.14(I) states that this load calculation provision does not apply to receptacles on small-appliance and laundry branch circuits in dwelling units. Receptacle outlets of 15- and 20-ampere ratings in dwellings are included in the general lighting-load calculations of 220.12. No additional load calculation is required for such outlets. Next month’s column continues the discussion of load calculations.               

MILLER, owner of Lighthouse Educational Services, teaches custom-tailored classes and conducts seminars covering various aspects of the electrical industry. He is the author of Illustrated Guide to the National Electrical Code and NFPA’s Electrical Reference. For more information, visit his Web site at www.charlesRmiller.com. He can be reached by telephone at 615.333.3336, or via e-mail at .

Receptacles are generally not considered continuous loads. The load for a general-use receptacle outlet in a non-dwelling occupancy is 180VA per strap [220.14(I)]. The maximum number of receptacle outlets permitted on a commercial or industrial circuit depends on the circuit ampacity. Calculate the number of receptacles per circuit by dividing the VA rating of the circuit by 180VA for each receptacle strap (also called a yoke), as shown in Fig. 2.

Based on the Art. 100 definition, a duplex receptacle is two receptacles on the same yoke. For the purposes of this calculation, a single receptacle or a duplex receptacle each count as 180VA [220.14(I)].

Calculate receptacle loads at not less than 180VA per outlet (strap) per 220.14(I) and fixed multioutlet assemblies per 220.14(H). According to 220.44, you can add these calculated loads to the lighting loads and apply the lighting load demand factors given in Table 220.42. Alternatively, you can use the demand factors for receptacles given in Table 220.44, which are as follows:

Calculate the receptacle load using 180VA for each single or multiple receptacle on one yoke or strap [220.14(I)].

The receptacle calculated load for office buildings and banks is the larger calculation of (1) or (2):

  1. Determine the receptacle calculated load at 180VA per receptacle yoke [220.14(I)], then apply the demand factor from Table 220.44.
  2. Determine the receptacle calculated load at 1VA per sq ft.

It's common not to know the exact number of receptacles that will eventually be installed in an office building or bank. The main structure is built first, then individual office space that's rented out to each tenant will often have a custom installation — or a new tenant will remodel the space to fit his or her needs. A calculation of 1VA per square foot allows a generic feeder/service demand for general receptacles.

What is the receptacle calculated load for an 18,000-sq-ft bank/office building containing 160 15A and 20A, 125V receptacles (straps)? [220.14(K)(1)], as shown in Fig. 3.

160 receptacles (straps) x 180VA [220.14(I)] = 28,800VA

Total receptacle load = 28,800VA

First 10,000VA at 100% (10,000VA x 1.00 = 10,000VA)

Remainder at 50% (18,800VA x 0.50 = 9,400VA) [Table 220.44]

Receptacle calculated load = 19,400VA

Compare this to the 1VA per sq ft method [220.14(K)(2)]

18,000 x 1VA per sq ft = 18,000VA (smaller answer, omit)

Sign circuits

The NEC requires each commercial occupancy accessible to pedestrians to have at least one 20A branch circuit for a sign [600.5(A)]. The load for the required exterior sign or outline lighting must be a minimum of 1,200VA [220.14(F)]. A sign outlet is a continuous load, and the feeder/service conductor must be sized at 125% of the continuous load [215.2(A)(1) and 230.42].

What is the feeder/service conductor calculated load for one electric sign (Fig. 4)?

Feeder/service calculated load = 1,200VA x 1.25 = 1,500VA

Commercial/industrial vs. residential

You've probably noticed that receptacle calculations for commercial/industrial applications differ from those that apply to residential applications. The differences exist because in residential locations, the receptacles are generally placed much closer together for convenience purposes but used in a diverse manner — so that all receptacles are not heavily loaded during all periods of time. In commercial occupancies, there are fewer rules governing receptacle placement, so they may be placed as needed, but may be called into use more often and for longer periods of time. In dwelling units, the receptacle load is included in the general lighting load VA calculated according to Table 220.12 and is then subject to the demand factors of Table 220.42. The 180VA per receptacle strap allowance does not apply to dwelling unit calculations.

In Part 1, we looked at how to calculate commercial loads using the standard method. You can save time by using the optional method. The optional method calculations are located in Part IV of Art. 220. The optional method calculations vary according to the type of building:

  • New dwelling units (220.82)
  • Existing dwelling units (220.83)
  • Multifamily dwellings (220.84)
  • Schools (220.86)
  • New restaurants (220.88)

All-electric restaurant

If a restaurant has electric space heating, electric air-conditioning, or both, you can use the optional method, which consists of the following two steps:

  1. Determine the total connected load. Add the nameplate rating of all loads at 100%, including both the air-conditioning and heating load [Table 220.88 Note].
  2. Apply the demand factors from Table 220.88 to the total connected load calculated in Step 1.

An example will help illustrate how the optional method works for restaurants. What's the calculated load for an all-electric restaurant (120/208V, 3-phase) that has a total connected load of 300kVA?

Total connected load = 300kVA

First 200kVA at 80% (200kVA x 0.80 = 160kVA)

Next 201kVA to 325kVA at 10% (100kVA x 0.10 = 10kVA

Total calculated load = 170kVA

I = VA ÷ (E x 1.732)

I = 170,000VA ÷ (208V x 1.732)

I = 170,000VA ÷ 360V = 472A

Paralleling two conductors per phase: 472A ÷ 2 raceways = 236A

250kcmil is rated 255A at 75ºC: 255A x 2 conductors (in parallel) = 510A

The minimum neutral size allowed when paralleling conductors is 1/0 AWG [250.24(C)(2) and 310.4].

What size grounding electrode conductor do you need if the service uses two sets of 250kcmil conductors in parallel?

First, find the equivalent area of the parallel conductors:

250kcmil x 2 conductors = 500kcmil [Table 250.66, Note 1]

500kcmil requires a 1/0 AWG grounding electrode conductor [Table 250.66].

The largest grounding electrode conductor to a ground rod is 6 AWG. The largest to a concrete encased electrode (Ufer) is 4 AWG [250.66(A) and 250.66(B)].

Not all-electric restaurant

What if the restaurant isn't all-electric? Try calculating the load for a not all-electric restaurant (120/208V, 3-phase) that has a total connected load of 300kVA.

Total connected load = 300kVA

First 200kVA at 100% (200kVA x 1.00 = 200kVA

201kVA to 325kVA at 50% (100kVA x 0.50 = 50kVA

Total calculated load = 250kVA

I = VA ÷ (E x 1.732)

I = 250,000VA ÷ (208V x 1.732)

I = 250,000VA ÷ 360V = 694A

Paralleling two conductors per phase: 694A ÷ 2 raceways = 347A

500kcmil is rated 380A at 75°C: (380A x 2 = 760A).

When a calculation result does not correspond to a standard overcurrent protection size, we are allowed to round up to the next standard size, as long as it does not exceed 800A [240.4(B)]. This would allow the use of an 800A overcurrent device [240.6(A)]

The minimum neutral size when paralleling conductors is 1/0 AWG [250.24(C)(2) and 310.4].

Fortunately, you don't have to use both the standard and optional methods and then pick the one that is the larger. You are allowed to use either approach, so you can save time by using the optional method.